Setebos 2S
A control and measurement unit designed for the supervision and control of objects, recording environmental parameters such as temperature and humidity. Additionally, through appropriate inputs, events of violating the facility space, flooding, etc. can be recorded. Moreover, the device enables remote control of devices located in the monitored facility.
Control and measuring unit Setebos 2S

Properties and Benefits
- 1x 10 / 100Mbit / s Ethernet, GSM - management / monitoring
- 1-wire interface for external sensors, temperature, humidity, other measured values, dew point calculation or multi-point external temperature monitoring
- Control of relay outputs, NO / NC connectors
- Digital inputs with optoisolation of the "dry contact" type
- 3x RS232 / RS485 / RS422 interfaces with galvanic separation, for transferring the RS contact of foreign device management or for communication with sensors, including virtual-com, SSH console
- Building automation control with the cooperation of an external mobile application (tablet, phone) or an application for a PC
- Possibility to connect expansion modules: additional inputs, outputs, size measurements, measurement of external voltages 0-60V DC
- Remote reading of device parameters and states via the Modbus / TCP protocol
- HTTP / HTTPS, SNMP / SNMPv3, SMTP, TELNET / SSH, SNTP, Syslog management
- USB CLI OTG
- Working temperature from -40 to + 70 ° C
- Rugged metal housing IP-30 DIN
- DC power supply
Catalog card

Control and measuring unit Setebos 2S
Product card
Haven’t found the answer to your bothering questions?
Ethernet interfaces
1x RJ45 10/100Mbps – zarządzanie/ monitoring |
Temperature and humidity measurement interface
Temperature measurement range: -40 – +125 ° C |
Temperature measurement accuracy: +/- 0.2 ° C for 25 ° C |
Humidity measuring range: 0-100% RH |
Accuracy of humidity measurement: +/- 2% RH |
The maximum number of sensors T = 4 and T / H = 2 |
Connector: crimp screw connections |
RS232 / 485/422 interfaces
Transmission speed
|
Configuration of the interface type
|
Connector: screw |
GSM modem
1 (2) x GSM 2 / 3G / (4G LTE) modem |
CDMA / HSPA / UMTS / EDGE / LTE standards |
Radio frequencies: 800/900/1800/2100 / 2100MHz |
1 (2) x SIM card |
2 (3) x antenna with SMA connector |
Signaling of operating states and signal quality |
Automatic logging and establishing a packet session in the APN, after unsuccessful attempts, a hardware restart of the device |
Management
SNMP v1 / 2c / 3, TELNET, SNTP, Syslog |
HTTP / HTTPS protocol – management via a web browser |
SSH |
SMTP – sending e-mail in case of failure |
Remote reading of device parameters and states via the Modbus / TCP protocol |
1-wire interface
Baud rate 0 – 16.3 kbit / s |
Range ≤ 100m |
Connector: crimp screw connections |
Digital outputs
Number of outputs – 4/8 |
Type of outputs – “relay contact” |
Maximum switching current – 0.5A, 48VDC |
One output (option 2/3 for Gx) max. switching current – 8A, 250VAC, 8A 24VDC |
One output (option 2/3 for Gx) max. switching current – 8A 24VDC |
Connector: screw |
Digital inputs
Number of inputs – 2/4 |
Galvanically isolated inputs |
Input type – dry contact |
Connector: screw |
USB Host
1x USB CLI OTG |
Physical features
Can be mounted on a DIN rail |
Metal housing IP-30 |
Dimensions: 135x120x145mm (with GSM module) |
Weight: 1.2 kg |
Work environment requirements
Standard working temperature: -40 to + 70 ° C |
Active cooling / heating elements are missing from the unit and no external sources are required |
Standard operating ambient humidity: 0 to 95% (non-condensing) |
Location type: class C in accordance with PN-EN 60870-2-2 – sheltered locations |
Protection class in accordance with IP-30 |
Power
In the range of 9-36V DC or in the range of 18-60V DC |
Screw connection |
Power consumption up to 9W |
More information can be found in the product catalog